Q&A | Condenser Relief Valves
Question: Are pressure relief valves required to be installed on an evaporative condenser?
Please visit our website for more information on this topic.
Answer: This is a very good question and one that gets asked frequently. Since an evaporative condenser is not a pressure vessel, it is not a black and white requirement as it is for the vessels throughout a refrigeration system. However, the condenser has the potential to contain large quantities of ammonia and if isolated incorrectly can lead to hydrostatic expansion and equipment rupture. The most current codes are now addressing this danger with greater clarity. Below you can read a section from ANSI/ASHRAE 15- Safety Standard for Refrigeration Systems. It addresses the issue pretty succinctly:
If you are looking for more details, kindly visit CHT TECK.
In other words, if ammonia can be trapped in an evaporative condenser during normal operation, then relief valves must be installed. If ammonia can only be trapped during maintenance (temporary operations) then administrative controls (procedures) are sufficient to prevent over-pressurization. Usually the question I ask to get to the bottom of this is…”Does the facility isolate the condenser as part of normal operation because of fluctuating load patterns?” If the answer is “Yes“, then relief valves should be installed on each evaporative condenser circuit.
IIAR also addresses the issue in a similar fashion ANSI/IIAR 2- Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigerating Systems. You can read their requirements below:
Contact us to discuss your requirements of Evaporative Condenser(es,vi,ar). Our experienced sales team can help you identify the options that best suit your needs.

Comments